Troubleshooting

The VHSC module returns diagnostics in word 1 of the block
transfer read (BTR) to the processor. These codes are identified
below.

Diagnostics Reported in Word 1 of BTR

Word

Bit

Indication

1

Bit 00

PowerĆup bit indicates whether a successful BTW with valid data has

occurred since powerĆup, or since last switched from Program to Run mode.

Bit 0 = 0 Ć Successful BTW

Bit 0 = 1 Ć BTW has not occurred

Bits 01Ć03 Not used

Bits 04Ć07 New data bits. Bit 04 corresponds to counter 0, bit 05 to counter 1, etc.

Bits 08Ć15

Diagnostic byte. This byte is always in BCD format. This byte indicates which

word (1Ć64) in the BTW file that was incorrect, or one of the following error

codes. The codes are as follows:

Code

87

Preset or reset illegal for counter 0 with frequency mode

88

Preset or reset illegal for counter 1 with frequency mode

89

Preset or reset illegal for counter 2 with frequency mode

90

Preset or reset illegal for counter 3 with frequency mode

91

Store count illegal for counter 0 with frequency mode

92

Store count illegal for counter 1 with frequency mode

93

Store count illegal for counter 2 with frequency mode

94

Store count illegal for counter 3 with frequency mode

95

Preset greater than rollover for counter 0

96

Preset greater than rollover for counter 1

97

Preset greater than rollover for counter 2

98

Preset greater than rollover for counter 3

99

BTW length invalid Ć length not equal to 0, 1, 2, 4, 12, 20, 24, 29,

34, 39, 44, 49, 54, 59, 64.

In this chapter, you learned how to interpret the module indicators,
and the meanimg of the error codes returned by the module.

Diagnostic Codes

Returned by the Module