2–6 Installing the Very High-Speed Counter Module

Figure 2.3

Connection Diagram for Very High Speed Counter Module (1771ĆVHSC)

(See applicable codes and laws.)

Note: Terminals on the left are

even numbered (2 thru 40), and

terminals on the right are odd

numbered (1 thru 39).

Channel A/Channel A Return
Channel B/Channel B Return
Gate Not input
Gate Not input

Channel A/Channel A Return

Channel A/Channel A Return

Channel B/Channel B Return
Gate Not Input

Channel B Input
Channel A Input
Customer V

CC

0Ć1

Output 1

Output 3
Customer V

CC

4Ć5

Output 5
Customer V

CC

6Ć7

Output 0

Customer Common 0Ć1

Customer Common 2Ć3
Output 4
Customer Common 4Ć5
Output 6

Channel B Input
Gate Input

Gate Input

Channel A Input
Channel A Input
Channel B Input
Gate Input

2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40

Channel A Input

Channel B Input

Gate Input

Customer V

CC

2Ć3

Output 7

Channel B/Channel B Return

Gate Not Input

Output 2

Customer Common 6Ć7

(Actual wiring runs in this direction.)

Counter 0

Counter 1

Counter 2

Counter 3

Channel A/Channel A Return

Channel B/Channel B Return

10689ĆI

The sensor cable must be shielded. The

shield must:

extend the length of the cable, but be

connected only at the 1771 I/O chassis

extend up to the point of termination

Important: The shield should extend to the

termination point, exposing just

enough cable to adequately

terminate the inner conductors.

Use heat shrink or another

suitable insulation where the wire

exits the cable jacket.

When using shielded cable, ground the foil shield and drain wire
only at one end of the cable. We recommend that you wrap the foil
shield and drain wire together and connect them to a chassis
mounting bolt (Figure 2.4). At the opposite end of the cable, tape
exposed shield and drain wire with electrical tape to insulate it from
electrical contact.

Grounding the VHSC

Module Wiring