6 - troubleshooting, Chapter objectives, Using the indicators – Rockwell Automation 1771-VHSC , D17716.5.74 Very High S User Manual

Page 51: Troubleshooting, Chapter

Advertising
background image

Chapter

6

Troubleshooting

In this chapter you will learn how to troubleshoot your VHSC
module using the indicators on the front of the module, and the
troubleshooting flowchart.

The indicators on the front of the module are an aid in
troubleshooting. These indicators consist of:

active indicator

input indicators

output indicators

fault indicator

The active indicator is on when the module has successfully powered
up. When an input indicator (A, B) is on, it indicates that the input is
high. When the output indicator is on, it indicates that the module
has commanded the output to be on. When a gate/reset indicator (G)
is on, its input is high. Since that signal can be inverted, it does not
indicate whether the signal on that terminal is necessarily logically
true.

A troubleshooting chart is shown below.

Troubleshooting Chart

Indication

Probable Cause

Corrective Action

Active LED ON

The module has successfully powered up.

Normal. No action required.

Active OFF

The module has not powered up successfully.

Check fault light, and rack power supply.

Input LED ON

A signal is available at the designated input

terminal (high).

Normal. No action required.

Input LED OFF

A signal is not available at the designated input

terminal (low).

Normal. No action required.

Fault LED ON

Internal problem.

Power down the module, reseat in I/O chassis, and

restore power. If the fault LED remains on, replace

module.

Output LED ON

The module has commanded an output on.

Normal. No action required.

Output LED OFF

The output is off.

Normal. No action required.

Chapter Objectives

Using the Indicators for

Troubleshooting

A0 A1 A2 A3

B0 B1 B2 B3

00 02 04 06

01 03 05 07

ACTIVE

INPUTS

FAULT

OUTPUTS

Input Indicators

Output Indicators

Fault Indicator

Active Indicator

G0 G1 G2 G3

10716ĆI

Advertising