1–11

Overview of the Very High Speed Counter Module

Table 1.A

Relationship Between Sampled Pulses and Input Frequency

Input Frequency at Gate/Reset

Terminal in Hz

(words 11Ć18 in BTR)

Sampled Pulses for 1/2 Cycle

of Gate/Reset Pulse

(words 3Ć10 in BTR)

2

1 meg

5

400K

10

200K

20

100K

50

40K

100

20K

200

10K

500

4K

1KHz

2K

2KHz

1K

5KHz

400

10KHz

200

20KHz

100

50KHz

40

100KHz

20

200KHz

10

Operation of scaler
In period/rate mode, the scaler lets the incoming pulse train at the
gate/reset pin be divided by a user defined number. Acceptable
values for the scaler are 1, 2, 4, 8, 16, 32, 64 and 128. There is one
scaler value for each counter. The default value for each scaler is 1.
Note: A 0 is equivalent to 1.

!

ATTENTION: Sample period times scaler must be
less than 0.25 seconds or the counter will overflow
without providing an overflow indication.

Connection to Counter Inputs
The only input to the module in the period/rate mode is made to the
gate/reset terminal. The counter inputs (channel A and B) are not
used in the period/rate mode.