Rockwell Automation 1771-VHSC , D17716.5.74 Very High S User Manual

Page 43

Advertising
background image

4–4

Configuring Your Module

Description

Bits

Word

Word 3

bits 00Ć02

Determine rate measurement mode, encoder mode, counter mode or

period/rate mode for COUNTER 0.

Mode

Bit

02

01

00

Counter mode

0

0

0

Encoder X1 mode

0

0

1

Encoder X4 mode

0

1

0

Counter not used

0

1

1

Period/rate mode

1

0

0

Rate Measurement mode

1

0

1

Continuous/rate mode

1

1

0

bit 03

Not used

bits 04Ć06

Determine store count mode for COUNTER 0.

Mode

Bit

06

05

04

Store count mode not used for counter 0

0

0

0

Mode 1 (store/continue) used

0

0

1

Mode 2 (store/wait/resume) used

0

1

0

Mode 3 (storeĆreset/wait/start) used

0

1

1

Mode 4 (storeĆreset/start) used

1

0

0

bit 07

Invert signal bit for gate/reset terminal.

0 = Not inverted

1 = Inverted

bits 08Ć10

Determine rate measurement mode, encoder mode, counter mode or

period/rate mode for COUNTER 1.

Mode

Bit

10

09

08

Counter mode

0

0

0

Encoder X1 mode

0

0

1

Encoder X4 mode

0

1

0

Counter not used

0

1

1

Period/rate mode

1

0

0

Rate Measurement mode

1

0

1

Continuous/rate mode

1

1

0

bit 11

Not used

bits 12Ć14

Determine store count mode for COUNTER 1.

Mode

Bit

14

13

12

Store count mode not used for counter 1

0

0

0

Mode 1 (store/continue) used

0

0

1

Mode 2 (store/wait/resume) used

0

1

0

Mode 3 (storeĆreset/wait/start) used

0

1

1

Mode 4 (storeĆreset/start) used

1

0

0