2–5

Installing the Very High-Speed Counter Module

Figure 2.2

Setting the Configuration Jumpers

Filter Jumper

Position

Voltage Jumper

Position

Description of Operation

Down

Down

12Ć24V High Speed (factory default setting)

Down

Up

5V High Speed

Up

Down

12Ć24V with low speed filter

Up

Up

5V with low speed filter

FILTER

HI SPEED

5V

12Ć24V

A0

B0

G0

10688ĆI

*

*

In the filter position, the module will not see frequencies above 100Hz.

3. Reposition the cover and secure with the 4 screws removed in

step 1.

Connect your I/O devices to the 40-terminal field wiring arm (cat.
no. 1771-WN) shipped with the module (Figure 2.3). Attach the
field wiring arm to the pivot bar at the bottom of the I/O chassis.
The field wiring arm pivots upward and connects with the module so
you can install or remove the module without disconnecting the
wires.

Connecting Wiring