Examples of period/rate and continuous/rate – Rockwell Automation 1771-VHSC , D17716.5.74 Very High S User Manual

Page 76

Advertising
background image

Period/Rate and Continuous/Rate Examples

E–5

The 4MHz count, total count, frequency and new data bit reported to
the programmable controller will be updated every scaler number of
pulses. And 250–260ms after the last pulses stop, the 4MHz count
will go to 999,999, the frequency will go to 0 and the new data bit
will be set. The outputs are updated dynamically on the module as
the 4MHz count increases.

If less than the scaler number of pulses occurs in 250ms, but at least
1/2(scaler) + 1 pulses occur in 250ms, the operation of 4MHz count
and frequency will be accurate, but may appear intermittent due to
“left over” pulses. The outputs will always update every scaler
number of pulses regardless of the update of the 4MHz count.

Note: “Left over” pulses are pulses that occur that are not divisible
by the scaler. (i.e. With a scaler of 4, if 6 pulses occur there are 2
“left over” pulses.)

The following waveforms illustrate the difference between period/rate
and continuous/rate. All waveforms were initiated by applying a 50Hz
signal at the gate/reset terminal of a counter configured for either
period/rate or continuous/rate. The output configuration remained
constant with an ON value of 20,000 counts and an OFF value of
80,000 counts. Only the scalar mode was varied to show the operation
of the two modes.

Figure E.1

Operation of Outputs in Period/Rate and Continuous/Rate with

Scaler = 1

50Hz at Gate/Reset

50% Duty Cycle

Scaler = 1

Counter times

width of pulse

4MHz count = 40,000

Counter

Idle

CHANNEL IN PERIOD/RATE

CHANNEL IN CONTINUOUS/RATE

ON at 20,000

OFF at 80,000

Scaler = 1

ON at 20,000

OFF at 80,000

Scaler = 1

4MHz Count

= 40,000

4MHz Count = 40,000

4MHz Count

= 20,000

Examples of Period/Rate and

Continuous/Rate