3–2

Module Programming

Figure 3.1 below shows a sample PLC-2 program.

Figure 3.1

PLCĆ2 Family Sample Program Structure

EN

FILE TO FILE MOVE

COUNTER ADDR:

POSITION:

FILE LENGTH:

FILE A:

033

1

18

301-322

DN

FILE R:

RATE PER SCAN:

331-352

18

07

17

15

4

110

033

033

EN

DN

06

110

010

110

06

06

2

EN

BLOCK TRANSFER READ

DATA ADDRESS:

MODULE ADDRESS:

BLOCK LENGTH:

030

100

00

DN

FILE:

301-400

07

110

010

110

07

07

1

BTR

BLOCK TRANSFER WRITE

DATA ADDRESS:

MODULE ADDRESS:

BLOCK LENGTH:

031

100

00

FILE:

201-300

PUT

032

G

032

0

0

3

BTW

FFM

The VHSC module is located in rack 1, module group 0, slot 0. The data address 030 is among the first available timer/counters used for block transfer.

The default block length of 0 results in a 18 word block transfer read. The module status data is returned to the processor starting at address 301.

If a block length other than 0 is specified for the BTR or BTW the BTR and BTW cannot be enabled during the scan.

VHSC BTR Data Address

VHSC BTR

Done Bit

VHSC BTW

Enable Bit

06

010

The VHSC module is located in rack 1, module group 0, slot 0. The data address 031 is among the first available timer/counters used for block transfer.

The default block length of 0 results in a 64 word block transfer write. The module configuration data is stored starting at address 201. The preconditions

could also include the configuration bit (word 1, bit 0) to limit the block transfer write.

VHSC BTW

Done Bit

VHSC BTR

Enable Bit

07

010

This rung is used to place a zero between the first available timer counters used for all block transfers and those used throughout the rest of

the program.

This rung uses a BTR done bit to trigger a move of the count data stored at 301 to a buffered location at 331. The program should access all data

from the buffered file (count 0 MSD would be located in word 333 and the LSD in word 334.)