Rockwell Automation 1771-IR Series D RTD Input Module User Manual User Manual

Page 12

Advertising
background image

1–2

Overview of the RTD Input Module

Publication 1771Ć6.5.129 - March 2000

When using 10 ohm copper RTDs, you must dedicate your module
for exclusive use with 10 ohm copper RTDs. You can configure the
module to accept signals from any combination of 100 ohm platinum
and other types of non–copper RTDs. Both cases are determined by
block transfer write (BTW) selection.

The processor transfers data to and from the module using block
transfer write (BTW) and block transfer read (BTR) instructions in
your ladder diagram program. These instructions let the processor
obtain input values and status from the module, and let you establish
the module’s mode of operation (see below).

1. The processor transfers your configuration data and calibration

values to the module using a block transfer write instruction.

2. External devices generate analog signals that are transmitted to

the module.

Communication Between Processor and Module

Memory

User Program

To Output Devices

PC Processor

(PLC-5/40 Shown)

RTD Input Module

1771-IR Series B

BTW 1

BTR 4

5

6

2

3

12933-I

18

16

14

12

10

8

6

4

2

RTD

3. The module converts analog signals into binary or BCD format,

and stores theses values until the processor requests their
transfer.

4. When instructed by your ladder program, the processor performs

a read block transfer of the values and stores them in a data table.

How Analog Modules

Communicate with

Programmable Controllers

Advertising