The complete configuration block for the block transfer write to the
module is defined in below.

Configuration Block for RTD Input Module Block
Transfer Write

Dec. Bit

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Octal Bit

17

16

15

14

13

12

11

10

07

06

05

04

03

02

01

00

1

Sample Time

(for RTS)

Data

Format

RTD

Type

Units of

Measure

Single channel in ohms

2

10 ohm resistance @ 25

o

C

3

Channel 1 Bias

4

Channel 2 Bias

5

Channel 3 Bias

6

Channel 4 Bias

7

Channel 5 Bias

8

Channel 6 Bias

9

Channel 1 calibration

10

Channel 2 calibration

11

Channel 3 calibration

12

Channel 4 calibration

13

Channel 5 calibration

14

Channel 6 calibration

15

Auto-calibration request word

Bit/word descriptions of BTW file words 1 (configuration), 2
(resistance value of 10 ohm copper RTDs), 3 through 8 (individual
channel bias values) and 9 through 14 (individual channel calibration
words) are presented below. Enter data into the BTW instruction
after entering the instruction into your ladder diagram.

Bit/Word Definitions for RTD Input Module

Word

Bits

Description

Word 1

bits 00-05

If any of these bits are set, the corresponding input channel will be

reported in ohms. If RTDs other than 10 ohm copper or 100 ohm

platinum are used you must report those channels in ohms, not

degrees. Data format on a channel displayed in ohms will default to

binary.

bits 06-07

Determines what units of measure the module reports.
Units of measure

Bits

07

06

Degrees C

0

0

Degrees F

0

1

Configuring Block for a

Block Transfer Write

Bit/Word Descriptions