Configuring Your RTD Module

Publication 1771Ć6.5.129 - March 2000

You must indicate what format will be used to read data from your
module. Typically, BCD is selected with PLC–2 processors, and
binary (also referred to as integer or decimal) is selected with PLC–3
and PLC–5 processors. See below and Appendix C for details on
Data Format.

Selecting Format for Reading Data

Decimal Bit 10

Octal Bit 12

Decimal Bit 9

Octal Bit 11

Data Format

0

0

BCD

0

1

2's complement binary

1

0

Signed magnitude binary

1

1

Same as signed magnitude binary

The RTD input module accepts the following types of RTD inputs:

RTD

Temperature Range

Indication Word 1,

Bit 10

Ohms

o

C

o

F

Platinum -200 to +870

o

C (-328 to 1598

o

F) Underrange

0

1.00

-200

-328

Overange

600.00

870

1598

Copper

-200 to +260

o

C (-328 to 500

o

F) Underrange

1

1.00

-200

-328

Overrange

327.67

260

500

The units of measure reported by the RTD module are selected by
setting bits 06–07 in BTW word 1.

Units of Measure

Bit

07

06

Degrees C

0

0

Degrees F

0

1

Ohms

1

0

Not used

1

1

If any of bits 0–5 are set (1), the corresponding input channel will be
reported in ohms.

Data Format

RTD Type

Units of Measure