Calibrating Your Module

Publication1771Ć6.5.129 - March 2000

Gain Calibration

Calibrating gain requires that you apply 402.00 ohms across each
input channel.

Normally all inputs are calibrated together. To calibrate the gain of
an input, proceed as follows:

1. Connect 402.00 ohm resistors across each input channel as shown

in Figure 6.2 below.

Figure 6.2

Resistor Location for Gain Calibration

18

16

14

12

10

8

6

4

2

C

B

A
C

B

A
C

B

A
C

B

A
C

B

A
C

B

A

12935

Channel 1

Channel 2

Channel 3

Channel 4

Channel 5

Channel 6

Terminal

Identification

402.0 ohm Resistor

Repeat for

each channel

2. Apply power to the module.

3. After the connections stabilize, request the gain calibration by

setting bit 01 in BTW word 15 and sending a block transfer write
(BTW) to the module.

NOTE: Normally, all channels are calibrated simultaneously (bits
10–15 of word 15 are octal 0). To disable calibration on any channel,
set (1) the corresponding bit 10 through 15 of word 15.