Troubleshooting

Publication 1771Ć6.5.129 - March 2000

Table 7.A

Troubleshooting Chart for the RTD Input Module

(1771-IR/D)

Indication

Probable Cause

Recommended Action

Both LEDs are OFF

No power to module

Possible short on the module

LED driver failure

Check power to I/O chassis. Recycle as

necessary.

Replace module.

Red FLT LED ON and

Green RUN LED is ON

Microprocessor, oscillator or EPROM failure

Replace module.

Red FLT LED ON

If immediately after power-up, indicates RAM or

EPROM failure.

1

Replace module.

If during operation, indicates possible

microprocessor or backplane interface failure.

1

Replace module.

Green RUN LED is flashing

Power-up diagnostics successfully completed.

Normal operation.

If LED continues to flash, and write block transfers

(BTW) cannot be accomplished, you have a

possible interface failure.

Check ladder logic program. If correct,

replace module.

1

When red LED is on, the watchdog timer has timed out and backplane communications are terminated. Your user program should

monitor communication.

Status Reported in Words 1 and 2

Design your program to monitor status bits in words 1 and 2, and to
take appropriate action depending on your application requirements.
You may also want to monitor these bits while troubleshooting with
your industrial terminal. The module sets a bit (1) to indicate it has
detected one or more of the following conditions.

Status Reported in Words 1 and 2

Word

Bit

Indication

1

00-05

Data underrange. Bit 05 corresponds to channel 6, bit 04 corresponds

to channel 5, and so on. If input connections and resistances are

correct, this status may indicate failed communications between the

channel and microprocessor. If all channels are underrange, a blown

fuse or failed dc-dc converter may be the cause.

06

Successful power-up and module is waiting for configuration data. Bit

06 is reset after the first successful block transfer write.

07

EEPROM calibration constants could not be read. The module will

continue to operate but readings may be inaccurate.

Word 1 (cont.)

10-15

Data overrange. Bit 15 corresponds to channel 6, bit 14 corresponds

to channel 5, and so on. If input connections and resistances are

correct, this status may indicate a failed RTD functional analog block

(RTD FAB).

16

RTS timed out. The module updated its inputs before the processor

read them.

17

Not used.