Differences Between Series A RTD Modules and Series B. C and D RTD Input Modules

F–2

Publication 1771Ć6.5.129 - March 2000

When displaying copper (10mohm/bit resolution) in ohms, the
resistance will be provided up to 327.67 ohms at which point an
overrange will occur (overrange on the Series A was 20.72
ohms). Platinum (30mohm/bit resolution) will over range at
600.00 ohms but continue to measure until the input saturates
(Series A was 399.99 ohms). Underrange for the Series B will be
1 ohm but continue to display until the input can no longer track.
The Series A underranged at copper – 1.17 ohms; platinum –
18.39 ohms. The Series B continues to track beyond the under or
overrange, except overrange on copper which clamps at 327.67
ohms. The Series A clamped the reading at the under or
overrange value.

Open RTD detection (excitation signal disconnected) will flag an
Overrange instead of Underrange.

Open RTD detection is < 0.5 seconds.

Overrange will continue to function as a flag, even if single
channel ohms has been requested.

When a channel is displaying temperature and an overrange
is detected, BTR temperature data for that channel will be
clamped at the RTD maximum temperature (Platinum – 870

o

C

or 598

o

F with Overflow, if customer bias has not been applied;

Copper – 260

o

C or 500

o

F).

A block transfer with a word length of 00 will return with the
Series A block transfer default length (14 for a write; 8 for a
read). To access the auto–calibration word, the block transfer
length must be set to 15 for a write and 9 for a read.

Auto–calibration can be performed on all channels
simultaneously or on selected channels. In either case, channels
being calibrated must be connected to the precision calibration
resistors.

The Series B module requires approximately 2 seconds to power
up.

The red LED is illuminated and the green LED is extinguished if
the watchdog timer times out.

This module employs a digital filter with 120dB/decade
rolloff from a corner frequency of 8 Hz.

This Series B module is NOT compatible with the 1771–EX
extender board. Use the 1771–EZ extender board with Series B.

Platinum RTD tables are based on IEC751 alpha = .00385. The
1771–IR/A was based on MINCO Products, Inc measurements of
IEC751 RTDs.

If the module is programmed for RTS = 0 and the PLC is
switched from run to program and back to run, an RTS timeout is
inhibited on the change from program to run.

In ohms mode, bias is able to produce a negative result.