4–6

Configuring Your RTD Module

Publication 1771Ć6.5.129 - March2000

Word

Description

Bits

Word 15

Auto-calibration request word - used to automatically calibrate

selected channels and save the calibration constants in EEPROM.

Bit 00

Offset calibration complete

Bit 01

Gain calibration complete

Bit 02

Save complete

Bit 06

EEPROM fault

Bit 07

Faulty calibration (no save)

Bits 08-15

(10-17)

Channel failed calibration

If zeroes are written to the module in all configuration positions, the
module will default to:

BCD format

100 ohm platinum RTD

temperature in degrees C

real time sampling = inhibited (sample time = 50ms)

In this chapter you learned how to configure your module’s
hardware, condition your inputs and enter your data.

Default Configuration for

the RTD Input Module

Chapter Summary