Rockwell Automation 1771-IR Series D RTD Input Module User Manual User Manual
Page 34
4–6
Configuring Your RTD Module
Publication 1771Ć6.5.129 - March2000
Word
Description
Bits
Word 15
Auto-calibration request word - used to automatically calibrate
selected channels and save the calibration constants in EEPROM.
Bit 00
Offset calibration complete
Bit 01
Gain calibration complete
Bit 02
Save complete
Bit 06
EEPROM fault
Bit 07
Faulty calibration (no save)
Bits 08-15
(10-17)
Channel failed calibration
If zeroes are written to the module in all configuration positions, the
module will default to:
•
BCD format
•
100 ohm platinum RTD
•
temperature in degrees C
•
real time sampling = inhibited (sample time = 50ms)
In this chapter you learned how to configure your module’s
hardware, condition your inputs and enter your data.
Default Configuration for
the RTD Input Module
Chapter Summary