Module scan time chapter summary – Rockwell Automation 1771-IR Series D RTD Input Module User Manual User Manual

Page 28

Advertising
background image

3–6

Module Programming

Publication 1771Ć6.5.129 - March 2000

A subsequent BTW operation is enabled by a pushbutton switch
(rung 2). Changing processor mode will not initiate a block transfer
write unless the first pass bit is added to the BTW input conditions.

Scan time is defined as the amount of time it takes for the input
module to read the input channels and place new data into the data
buffer. Scan time for your module is shown in specifications,
appendix A.

The following description references the sequence numbers in
Figure 3.4.

Following a block transfer write “1” the module inhibits
communication until after it has configured the data and loaded
calibration constants “2”, scanned the inputs “3”, and filled the data
buffer “4”. Write block transfers, therefore, should only be
performed when the module is being configured or calibrated.

Any time after the second scan begins “5”, a BTR request “6” can
be acknowledged.

When operated in real time sample mode (RTS) = 00, a BTR may
occur at any time after “4.” When operated in RTS = T, a BTR will
be waived until ”T” milliseconds, at which time 1 BTR will be
released.

Figure 3.4

Block Transfer Time

Block

Transfer

Write

Time

End of

Block

Transfer

Write

Configure

Time

1st Scan

2nd Scan

3rd Scan

Module available

to perform block

transfer

1

2

3

4

5

6

7

8

9

Internal Scan time = 50msec
T = 100ms, 200ms, 300ms ... 3.1sec.

In this chapter, you learned how to program your programmable
controller. You were given sample programs for your PLC–2, PLC–3
and PLC–5 family processors.

You also read about module scan time.

Module Scan Time

Chapter Summary

Advertising