Performing auto-calibration, Offset calibration – Rockwell Automation 1771-IR Series D RTD Input Module User Manual User Manual

Page 40

Advertising
background image

6–2

Calibrating Your Module

Publication1771Ć6.5.129 - March 2000

Calibration of the module consists of applying 1.00 ohm resistance
across each input channel for offset calibration, and 402.00 ohm
across each input channel for gain correction.

Offset Calibration

Normally all inputs are calibrated together. To calibrate the offset of
an input, proceed as follows:

1. Connect 1.00 ohm resistors across each input channel as shown in

Figure 6.1.

Figure 6.1

Resistor Location for Offset Calibration

18

16

14

12

10

8

6

4

2

C

B

A

C

B

A

C

B

A

C

B

A

C

B

A

C

B

A

12935

Channel 1

Channel 2

Channel 3

Channel 4

Channel 5

Channel 6

Terminal

Identification

1.00 ohm Resistor

Repeat for

each

channel

2. Apply power to the module.

3. After the connections stabilize, request the offset calibration by

setting bit 00 in block transfer write word 15 and sending a block
transfer write to the module. Refer to the table below.

Performing

Auto-calibration