Rockwell Automation 1771-IR Series D RTD Input Module User Manual User Manual

Page 56

Advertising
background image

Programming Examples

B–4

Publication 1771Ć6.5.129 - March 2000

2. Press [F8],[F5] and enter N7:60 to display the configuration

block.

The industrial terminal screen should like figure B.3.

Figure B.3

Sample PLC-5 Data File (Hexidecimal Data)

Address
N7:60
N7:70

3

0150
0000

5

0150

6

0150

7

0150

8

0000

9

0000

4

0150

2

0150
0000

1

0976
0000

0

5141
0000

The above data file would configure the module as follow:

copper RTDs on all inputs

temperature scale of Fahrenheit

channel 1 displayed in ohms

output data in BCD format

real time sampling set to a 1 second scan rate

copper RTD at 25

o

C is 9.76 ohms

all bias values set to subtract 0150

all calibration values set to 0

3. Enter the data corresponding to your bit selections.

4. [ESC] returns you to the main menu.