Rockwell Automation 1771-IR Series D RTD Input Module User Manual User Manual
Page 56
Advertising
![background image](/manuals/579137/56/background.png)
Programming Examples
B–4
Publication 1771Ć6.5.129 - March 2000
2. Press [F8],[F5] and enter N7:60 to display the configuration
block.
The industrial terminal screen should like figure B.3.
Figure B.3
Sample PLC-5 Data File (Hexidecimal Data)
Address
N7:60
N7:70
3
0150
0000
5
0150
6
0150
7
0150
8
0000
9
0000
4
0150
2
0150
0000
1
0976
0000
0
5141
0000
The above data file would configure the module as follow:
•
copper RTDs on all inputs
•
temperature scale of Fahrenheit
•
channel 1 displayed in ohms
•
output data in BCD format
•
real time sampling set to a 1 second scan rate
•
copper RTD at 25
o
C is 9.76 ohms
•
all bias values set to subtract 0150
•
all calibration values set to 0
3. Enter the data corresponding to your bit selections.
4. [ESC] returns you to the main menu.