Key the backplane connector, Install the module and field wiring arm – Rockwell Automation 1771-IR Series D RTD Input Module User Manual User Manual

Page 17

Advertising
background image

2–3

Installing the RTD Input Module

Publication 1771Ć6.5.129 - March 2000

Group your modules to minimize adverse affects from radiated
electrical noise and heat. We recommend the following.

Group analog input and low voltage dc modules away from ac
modules or high voltage dc modules to minimize electrical noise
interference.

Do not place this module in the same I/O group with a discrete
high-density I/O module when using 2-slot addressing. This
module uses a byte in both the input and output image tables for
block transfer.

Key the Backplane

Connector

Place your module in any slot in the chassis
except the leftmost slot which is reserved for
processors or adapters.

ATTENTION: Observe the
following precautions when
inserting or removing keys:

insert or remove keys with
your fingers

make sure that key placement
is correct

Incorrect keying or the use of a
tool can result in damage to the
backplane connector and possible
system faults.

!

Position the keying bands in the backplane connectors to correspond to

the key slots on the module.

Place the keying bands:

between 10 and 12

between 28 and 30

You can change the position of these bands if

subsequent system design and rewiring makes

insertion of a different type of module necessary.

Upper

Connector

11022ĆI

I/O chassis

!

ATTENTION: Remove power from the 1771 I/O
chassis backplane before you install the module.
Failure to remove power from the backplane
could cause:

Smodule damage

Sdegradation of performance

Sinjury or equipment damage due to possible
unexpected operation

Install the Module and

Field Wiring Arm

Advertising