4–5

Configuring Your RTD Module

Publication 1771Ć6.5.129 - March 2000

Word

Description

Bits

Word 1 Cont.

Ohms

1

0

Not used

1

1

bit 08 (10)

In temperature mode:

0 = Entire module is platinum

1 = Entire module is 10 ohm copper. Enter exact value in word 2.

In ohms mode:

0 = 30mohm/count resolution

1 = 10mohm/count resolution

bits 09-10

(11-12)

Data format bits tell module which format to use for reporting input

values to processsor
Format

Bits

12

11

4-digit BCD

0

0

2's complement binary

0

1

Signed magnitude (binary)

1

0

Not used

1

1

bits 11-15

(13-17)

Real time sample bits. See NO TAG.

Sample Time

17

16

15

14

13

0.1ms

0

0

0

0

1

0.5ms

0

0

1

0

1

0.6ms

0

0

1

1

0

0.7ms

0

0

1

1

1

0.8ms

0

1

0

0

0

0.9ms

0

1

0

0

1

1.0s

0

1

0

1

0

1.5s

0

1

1

1

1

2.0s

1

0

1

0

0

2.5s

1

1

0

0

1

3.0s

1

1

1

1

0

Word 2

If bit 10 is set in word 1, and temperature readings are desired, word

2 must also be used. Enter the exact resistance of 10 ohm RTD at

25

o

C in BCD. Range is 9.00 to 11.00 ohms. Values less than 9.00

ohms or greater than 11.00 ohms will default to 10.00 ohms.

Non-BCD values will also default to 10.00 ohms.

Words 3-8

Individual channel bias words entered in BCD. This value is

subtracted from the channel data in the BTR. The bias value is

always a positive number. Bias value range is 0<bias<9999.

Words 9-14

Individual channel calibration words.