Module status and input data, Chapter – Rockwell Automation 1771-IR Series D RTD Input Module User Manual User Manual

Page 35

Advertising
background image

Chapter

5

Publication 1771Ć6.5.129 - March 2000

Module Status and Input Data

In this chapter you will read about:

reading data from your module

input module read block format

Block transfer read programming moves status and data from the
input module to the processor’s data table in one I/O scan. The
processor user program initiates the request to transfer data from the
input module to the processor.

During normal operation, the read block transfer for this module
moves up to 8 words from the RTD module in one program scan.
The words contain module status and input data from each channel.
When a block transfer length of 0 is programmed, the
1771–IR/D will respond with the Series A default of 8 words.

The user program initiates the request to transfer data from the RTD
module to the processor.

Figure5.1

BTR Word Assignments for RTD Input Module

(1771-IR/D)

Decimal Bit

15

14

13 12 11 10 09 08

07

06

05 04 03 02 01 00

Octal Bit

17

16

15 14 13 12 11 10

07

06

05 04 03 02 01 00

1

0

RTS

Timeout

Channel Overrange

EEPROM

calibration

values not

readable

Power-

up

Channel Underrange

2

Not used

Channel Polarity

Not used

Channel Overflow

3

Channel 1 Data

4

Channel 2 Data

5

Channel 3 Data

6

Channel 4 Data

7

Channel 5 Data

8

Channel 6 Data

9

Auto-calibration Status Word

Chapter Objectives

Reading Data from the

RTD Module