Analog Encoder (AE) Servo Module 11

Publication 1756-IN047D-EN-P - March 2001

Wiring a Spring Clamp RTB

To wire a spring clamp RTB:

1. Strip a maximum of 7/16 inch (11mm) of insulation from the end of

your wire.

2. Insert the screwdriver into the outer hole of the RTB.

3. Insert the wire into the open terminal and remove the screwdriver.

Figure 6 Strain Relief Area

4. After you complete field-side wiring, secure the wires in the strain

relief area with a cable-tie.

Wiring a Cage Clamp RTB

To wire a cage clamp RTB:

1. Strip 5/16 - 3/8 inch (8 - 9.5mm) of insulation from the end of your

wire.

2. Insert the screwdriver into the open terminal.

Strain Relief Area