22 analog encoder (ae) servo module – Rockwell Automation 1756-M02AE Analog Encoder (AE) Servo Module Installation Instructions User Manual

Page 22

Advertising
background image

22 Analog Encoder (AE) Servo Module

Publication 1756-IN047D-EN-P - March 2001

Figure 19 OK Relay Pilot Duty Application Wiring

Assembling the Removable Terminal Block and Housing

To assemble the removable terminal block and housing:

1. Align the grooves at the bottom of each side of the housing with the

side edges of the RTB.

2. Slide the RTB into the housing until it snaps into place

IMPORTANT

When the OK Relay is loaded with an inductive load,
use a counter-EMF suppression diode across the load.
The maximum rating of the OK relay contacts must not
exceed 60V DC.

24 VDC

Field Power

Supply

+OK

-OK

General Cable

C0720

From 1756-M02AE

+

-

OK Relay

OK Relay
Contacts

Start

CR1

Stop

CR1

CR1

M1

+

-

24 VDC

Field Power

Supply

To User's circuitry

+OK

-OK

Advertising