28 Analog Encoder (AE) Servo Module

Publication 1756-IN047D-EN-P - March 2001

Understanding Module Status Using the DRIVE Indicator

Steady green
light

The axis is in the normal
servo loop active state.

None. The servo can may be changed by
executing motion instructions.

Flashing red
light

The axis servo loop error
tolerance has been
exceeded.

• Correct the source of the

problem.

• Clear the servo fault condition

using the Motion Axis Fault
Reset instruction.

• Resume normal operation.

Solid red light

An axis encoder feedback
fault has occurred.

• Correct the source of the

problem by checking the
encoder and power
connections.

• Clear the servo fault condition

using the Motion Axis Fault
Reset instruction.

• Resume normal operation.

If the DRIVE
LED displays:

Then the module status
is:

Take this action:

Off

• The axis is not

used.

• The axis is a

position-only axis
type.

• None, if the axis is not used or

is a position-only type.

• Otherwise, make sure the

module is configured, an axis
tag has been associated with
the module, and the axis type is
servo.

Flashing green
light

The axis drive is in the
normal disabled state.

None. The servo axis state can be
changed by executing motion
instructions.

If the FDBK
LED displays:

Then the module status
is:

Take this action: