34 Analog Encoder (AE) Servo Module

Publication 1756-IN047D-EN-P - March 2001

1)

Maximum wire size will require the extended depth RTB housing (1756-TBE).

2)

Use this conductor category information for planning conductor routing as described in the system
level installation manual.

3)

Refer to Industrial Automation Wiring and Grounding Guidelines, publication number 1770-4.1.

Installation Environment

This product must be mounted within a suitable system enclosure to prevent
personal injury resulting from accessibility to live parts. The interior of this
enclosure must be accessible only by the use of a tool.

This industrial control equipment is intended to operate in a Pollution Degree
2 environment, in overvoltage category II applications, (as defined in IEC
publication 664A) at altitudes up to 2000 meters without derating.

The following information applies when operat-
ing this equipment in hazardous locations:

Products marked “CL I, DIV 2, GP A, B, C, D” are suitable for use in Class I
Division 2 Groups A, B, C, D, Hazardous Locations and nonhazardous
locations only. Each product is supplied with markings on the rating
nameplate indicating the hazardous location temperature code. When
combining products within a system, the most adverse temperature code
(lowest “T” number) may be used to help determine the overall temperature

Environmental conditions

Operating temperature
Storage temperature
Relative humidity

0 to 60ºC (32 to 140ºF)
-40 to 85ºC (-40 to 185ºF)
5 to 95% noncondensing

Agency Certifications
When product is marked


Listed Industrial Control Equipment

Certified Process Control Equipment
Certified Class I, Division 2, Group A, B, C, D

Marked for applicable directives

Marked for all applicable acts