10-6 Troubleshoot the Card
Publication 1784-IN029C-EN-P - June 2001
9. If there are no conflicts, continue with step 10 below. If there are conflicts,
you may need to alter the settings of the conflicting devices to get the PCD 
card to work properly. First try unchecking the Use Automatic Settings box 
and then changing the memory or interrupt resources.
To change the resources:
a. Click on the resource you want to change.
b. Click the Change Setting button.
c. Change the memory or interrupt resources to a free memory or interrupt
resource.
10. Select My Computer
⇒
Properties
⇒
Device Manager.
11. Scroll through the list until you see the PCMCIA sockets entry.
TIP
To find free memory and interrupt resources on Windows 
95/98/Me systems, in the Device Manager window, right-click 
on Computer and select Properties. You see the Computer 
Properties screen, which shows you the resources in use.
TIP
Depending on your Windows 98 operating system, 
unchecking the Use Automatic Settings box may not be 
successful. Contact Rockwell Automation Technical Support 
for more information.