1771-6.4.5, 5 - configuring the loops, Configuring the loops, Chapter – Rockwell Automation 1771-TCM TEMPERATURE CONTROL User Manual
Page 36

Chapter
5
Publication 1771Ć6.4.5 - January 1997
Configuring the Loops
This chapter shows you how to configure the PID loops of the
1771-TCM module. This includes:
•
changing default loop names
•
configuration selections
•
thermocouple break detection
•
thermal integrity detection
•
alarm dead band
•
fine-tuning the loops
•
bringing up the Loop Configuration screen
•
entering configuration values
•
downloading configuration values
•
uploading configuration values
•
using one loop to configure another
To change default loop names:
1. At the Module List screen, select the module for which you want
to generate the loop list.
As you select a module on the Project screen, the loop list for that
specific module is displayed.
2. Select a loop.
3. From the
Loop pull-down menu, select Name.
The Loop-Name dialog box appears.
4. Enter a symbolic name for the loop.
5. Select
OK.
You see the loop list for the module.
Changing Default Loop
Names