Rockwell Automation 1771-TCM TEMPERATURE CONTROL User Manual

Page 59

Advertising
background image

7–2

Monitoring and Controlling the Loops

Publication 1771Ć6.4.5 - January 1997

The module status pane is used to display error messages. If the
number of current error messages exceeds the number of lines that
can be displayed, you can scroll thru the messages. The possible
error messages include the following:

high temperature alarm

low temperature alarm

high deviation alarm

low deviation alarm

high manipulated variable (M) alarm

low (M) alarm

input over range

input under range

TC break alarm

loss of thermal integrity

calibration fault

CJ under range

CJ over range

Auto-tuning terminated because of thermal integrity loss.

Auto-tuning terminated because of thermocouple break.

Heat auto-tuning inhibited because of starting conditions.

Cool auto-tuning inhibited because of starting conditions.

Set point will be reached before auto-tuning is complete.

Too much noise causing time constant to be 0.

Very small gain.

Set point exceeded before auto-tuning completed.

You may also see a message that says there is an error in a specific
word of the configuration block, the gains block, or the dynamic
block. In that case, refer to the user manual (publication
1771-6.5.120) to resolve the problem. This kind of problem would
most likely be a result of ladder logic errors such as writing over the
data-table interface area.