6–5

Tuning the Loops

Publication 1771Ć6.4.5 - January 1997

4. Select

Start Tuning.

Once the tuning process starts, the

Start Tuning selection becomes

Stop Tuning.

5. If at any time during the process you want to stop the auto-tuning,

select

Stop Tuning.

During auto-tuning, do not close the Tuning Assistant screen, as
this will prevent proper completion of tuning. You may minimize
the window if desired.

As the tuning process progresses, the tuning status for each loop
is reported as one of the following:

Unknown

In Process

Successful

Not Successful

When none of the loops are any longer reported as

In Process, the

auto-tuning is complete.

After auto-tuning is complete, you can monitor the the auto-tuning
results passed between the the TCM module and the PLC data table.
To monitor the auto-tuning results, from the

Module menu, select

Tuning Results.

The Auto-Tuning Result screen appears.

On this screen, for both heat and cool for each loop, the following
values are displayed:

controller gain

integral gain

derivative gain

slope (process gain for non-barrel loops)

time constant

dead time

Monitoring AutoĆTuning