Changing loop settings, Entering loop settings – Rockwell Automation 1771-TCM TEMPERATURE CONTROL User Manual

Page 60

Advertising
background image

7–3

Monitoring and Controlling the Loops

Publication 1771Ć6.4.5 - January 1997

To change loop settings, at the Loop Monitor screen, click on
Change Settings.

The Change-Settings dialog box appears.

Entering Loop Settings

Enter loop settings values within the stated ranges. In each case
where a decimal point is shown, if you want to enter a digit to the
right of the decimal point, you must type in the decimal point. The
decimal point is not inferred.

In this field:

Enter this value:

Loop Mode

Control, Monitor, or Off

Alarm Enable

Enable or Disable

Run/Standby

Run or Standby

Auto / Manual

Auto or Manual

SP Ramp Enable

enable or disable

SP Ramp Hold

Ramp or Hold

When Hold is selected during set point ramping, the ramp will

be stopped and the set point will hold at its current value.

When Ramp is selected, the ramp will continue normally. After

changing the selection, you must perform a download for your

change to take effect. If Setpoint Ramping is disabled, this

setting has no effect.

Note: This feature is only supported in Module Firmware

Version 3.3. and later.

Run Setpoint

0.0 thru 3276.7

°

Standby Setpoint

0.0 thru 3276.7

°

Manual Output Value

-100.00 thru +100.00

Changing Loop Settings