Rockwell Automation 1771-TCM TEMPERATURE CONTROL User Manual

Page 44

Advertising
background image

5–9

Configuring the Loops

Publication 1771Ć6.4.5 - January 1997

In this field:

Enter this value:

Run Setpoint

0.0 thru 3276.7

°

Standby Setpoint

0.0 thru 3276.7

°

Manual Output Value

-100.00 thru +100.00

SP Ramp Rate

0.00 thru 99.99

°

/min Ċ If enabled, the rate at which the current set point is increased or decreased to

reach the selected set point.

SP Ramp Enable

Toggles between enable and disable

Max. M Limit

-100.00 thru +100.00% Ċ The maximum M percentage allowable.

Min. M Limit

-100.00 thru +100.00% Ċ The minimum M percentage allowable.

Heat TPO Period

0 thru 100.00s Ċ The period in seconds at which the heat bit is cycled and the M is updated.

Heat Min. On Time

0 thru 100.00s Ċ The minimum time in seconds for which the heat bit is turned on during the TPO period.

If the calculated time is less than this minimum, the heat bit will not be turned on. This on time must be less

than the heat TPO period.

Cool TPO Period

0 thru 100.00s Ċ The period in seconds at which the cool bit is cycled and the M is updated.

Cool Min. On Time

0 thru 100.00s Ċ The minimum time in seconds for which the cool bit is turned on during the TPO period.

If the calculated time is less than this minimum, the cool bit will not be turned on. This on time must be less

than the cool TPO period.

High Temp Alarm

-3276.8 thru 3276.7

°

Ċ A temperature value at the high end of the sensor limit, but still below the

maximum temperature value.

Low Temp Alarm

-3276.8 thru 3276.7

°

Ċ A temperature value at the low end of the sensor limit, but still above the minimum

temperature value.

High Deviation Alarm

-3276.8 thru 3276.7

°

Ċ A value that specifies the greatest deviation above the set point that the process

can tolerate.

Low Deviation Alarm

-3276.8 thru 3276.7

°

Ċ A value that specifies the greatest deviation below the set point that the process

can tolerate.

Dead Band for Alarms

0.0 thru 10.0

°

Ċ Once the temperature alarm bits are on, they are kept on until the temperature drops

below the high alarm point by this value rises above the low alarm point by this value. The deadĆband value

applies to all alarms.

C Alarm Rate

-3276.8 thru 3276.7

°

/s Ċ If the rate of temperature (C) increase is greater than this value, the C rate alarm

is triggered. A value of 0.0 disables the C rate alarm.

Temperature Sensor Type

mV, B, E, J, K, R, S, T

Temperature Sensor Filter

When enabled, the C input is passed through a first order step equivalent lag filter. The filter's time constant

is determined by the value entered in the TC field.

Note: This feature is only supported in Module Firmware Version 3.3 and later.

Temperature Sensor TC

This is the filter time constant for the C input filter, and can range from 0.0 to 9.9 seconds. A setting of 0.0

effectively disables the filter.

Note: This feature is only supported in Module Firmware Version 3.3 and later.

Open Circuit Action

Disable Loop (M=0)

M = On Break M value Ċ The forced M value on TC break.

M = Manual Output value

Open Circuit M Value

-100.00 thru +100.00 Ċ The percentage value to force into the M output when a broken TC is detected.

TIL Configuration

Disable Loop (M=0)

M = On TIL M Ċ The forced M value on thermal integrity loss.

M = Manual Output value

TIL Forced M Value

-100.00 thru +100.00 Ċ The percentage value to force into the M output when thermal integrity loss is

detected.

TIL Period

0 thru 100 minutes

TIL Temp. Change

0 thru 100

°

Auto / Manual

Auto or Manual

Desired System Response

Slow, Medium, Fast, or Very Fast Ċ The system response desired as a result of autoĆtuning. This

selection will be used together with system parameter measured during autoĆtuning to generate the

autoĆtuning gains.

Control Type

Barrel or NonĆBarrel

Zone

Inner or Outer

Control Action

EĂ=ĂSP-C or EĂ=ĂC-SP