Alarm dead band tpo bit – Rockwell Automation 1771-TCM TEMPERATURE CONTROL User Manual

Page 41

Advertising
background image

5–6

Configuring the Loops

Publication 1771Ć6.4.5 - January 1997

Once the temperature alarm bits are on, they are kept on until the
temperature drops below the high alarm by the alarm dead-band
value or rise above the low alarm by this value. You specify the
temperature alarm dead band. This dead band provides a hysteresis
effect. The dead-band value applies to the high and low temperature
and deviation alarm values.

Low Alarm With Dead Band — When the temperature falls
below the user-defined low alarm value, the low alarm bit is
turned on. When the temperature rises above the level of the low
alarm value but still below the level of the dead-band value, the
low alarm bit remains on. Only when the temperature rises above
the dead-band level will the alarm bit be turned off.

High Alarm With Dead Band — When the temperature rises
above the user-defined high alarm value, the high alarm bit is
turned on. When the temperature falls below the level of the high
alarm value but still above the level of the dead-band value, the
high alarm bit remains on. Only when the temperature falls
below the dead-band level will the alarm bit be turned off.

High Alarm Level

Low Alarm Level

Time

Time

alarm on

The temperature passes thru

the dead band before the alarm

is turned on or off to provide

stability to alarm indicators

without dead band

with dead band

alarm off

dead band

dead band

Temperature

The ladder logic can send the TPO signal to a digital output module
to generate the control variable output signal to a digital temperature
control actuator.

X

Y

On

Off

Duty Cycle = Ċ

X

Y

TPO Bit

X = On Time
Y = TPO Period

You set the period and minimum on time for each loop’s heat and
cool TPO bits. You must set the TPO period to be less than the
system lag time (i.e. deadtime plus the time constant; this time is
available from the autotune results). If the TPO period is greater
than the lag time, the auto-tuning will calculate large gain values,
which will probably cause the temperature to overshoot the set point.

Alarm Dead Band

TPO Bit

Advertising