Preset function, Gate function – Rockwell Automation 1794-ID2 U.MNL INCREMENTAL ENCODER User Manual

Page 19

Advertising
background image

1–7

Overview of the Incremental Encoder Module

Publication 1794ĆUM015B-EN-P - May 2001

Preset Function

Use the preset function to copy a value from the preset register to the
counter register.

Counter Register

Counter Register

Preset Register

Logic

PresetEnable = 1

Preset

Z =

Preset Register

PresetReached = 1

PresetReached = 1

Method 1

Method 2

The flag PresetReached is set when the counter register and the
preset register are equal (if the counter preset is reached, or if the
counter has been loaded with the preset value). This flag is reset on a
positive edge of PresetReset after the operation and can only be set
after at least one additional counting pulse.

Gate Function

Use the gate function to determine when counting starts and
stops.You can use this function to measure distance.

The parameter GateControl determines the gate function. The gate
signal is connected to input G. It is a 2–bit binary code in write word
1 or 2, bits 09 and 10

Word

1 or 2

Gate Control Function

1 or 2

Bits

09 10

Binary 10

09 Gate Control bits

09-10

0

0

0

No gate function on input G (Count is independent)

1

0

1

Counting only if G = 1 (active)

2

1

0

Counting only if G = 0 (inactive)

3

1

1

Calibration if G = 1 and all other conditions are

fulfilled (refer to Calibrating the Module, chapter ?).

Gate Control = 1

Counter Register

Logic

A

G = 1

The counter is counting if G = 1.

Example