Rockwell Automation 1794-ID2 U.MNL INCREMENTAL ENCODER User Manual

Page 34

Advertising
background image

2–12

How to Install Your Incremental Encoder Module

Publication 1794ĆUM015B-EN-P - May 2001

Wiring connections for the 1794-ID2 incremental encoder Module

Terminal Base Units

1794-TB3, -TB3S

Terminal Base Units

1794-TBN, -TBNF

1

Signal

0V dc

12/24V dc

Signal

Input

incremental encoder Channel 0

A+

0

17

35

0

A-

1

18

36

1

B+

2

19

37

2

B-

3

20

38

3

Z+

4

21

39

4

Z-

5

22

40

5

G+

6

23

41

6

G-

7

24

42

7

incremental encoder Channel 1

A+

8

25

43

8

A-

9

26

44

9

B+

10

27

45

10

B-

11

28

46

11

Z+

12

29

47

12

Z-

13

30

48

13

G+

14

31

49

14

G-

15

32

50

15

0V dc

Terminals 16 and 33 (1794-TB2)

Terminals 16 thru 33 (1794ĆTB3, ĆTB3S)

Terminals 16 and 33

12/24V dc

Terminals 34 thru 51 (1794-TB3, -3S)

Terminals 34 and 51

1 Auxiliary terminal blocks are required when using these terminal base units.

!

ATTENTION: Total current draw through the
terminal base unit is limited to 10A. Separate power
connections to the terminal base unit may be necessary.

Advertising