Input, Output and Configuration Files for Analog Modules when used with ControlNet

Publication 1794ĆUM015B-EN-P - May 2001

Bit Description

Bit

Explanation

0

This bit is set (1) when an error is detected in slot position 0.

1

This bit is set (1) when an error is detected in slot position 1.

2

This bit is set (1) when an error is detected in slot position 2.

I/O Module Fault

3

This bit is set (1) when an error is detected in slot position 3.

I/O Module Fault

4

This bit is set (1) when an error is detected in slot position 4.

5

This bit is set (1) when an error is detected in slot position 5.

6

This bit is set (1) when an error is detected in slot position 6.

7

This bit is set (1) when an error is detected in slot position 7.

Node Address Changed

(Created by PLC-5

controller.)

8

This bit is set (1) when the node address switch setting has been

changed since power up.

I/O State (Created by

PLC-5 controller.)

9

Bit = 0 - idle

Bit = 1 - run

10 thru 15 Not used - set to 0.

Possible causes for an I/O Module Fault are:

transmission errors on the FLEX I/O backplane

a failed module

a module removed from its terminal base

incorrect module inserted in a slot position

the slot is empty

the slot contains a non–discrete module

The ControlNet adapter provides storage for alternate module output
data during communication faults or processor idle state. This “safe
state data” assures that a known output will be applied to the output
devices to maintain a previously designated safe operating condition
during the previously mentioned failure modes. The processor or
scanner software must include the means to specify this safe state
data for each module. If applicable, this data is sent in the
configuration block (see Image Table Mapping later in this chapter).

Device actions include:

communication fault behavior

idle state behavior

input data behavior upon module removal

Safe State Data

Device Actions