Rockwell Automation 1794-ID2 U.MNL INCREMENTAL ENCODER User Manual

Page 82

Advertising
background image

Specifications

A–2

Publication 1794ĆUM015B-EN-P - May 2001

Specifications - 1794ĆID2 2 Input Incremental Encoder Module

Environmental Conditions

Operational Temperature

Storage Temperature

Relative Humidity

Shock Operating

Nonoperating

Vibration

0 to 55

o

C (32 to 131

o

F) Note: Do not connect

maximum input voltage simultaneously to all inputs

if the module ambient temperature is expected to

exceed 40

o

C.

-25 to 70

o

C (-13 to 158

o

F)

5 to 90% noncondensing (operating)

5 to 80% noncondensing (nonoperating)

30 g peak acceleration, 11(+1)ms pulse width

50 g peak acceleration, 11(+1)ms pulse width

Tested 2 g @ 10-500Hz per IEC 68Ć2Ć6

Input Conductors

Wire

Category

Length (max)

Belden 8761

2

1

1000ft (304.8m)

Agency Certification

(when product is marked)

CUL certified

CUL listed - Class I, Division 2 Groups A, B, C, D

UL listed

CE marked for all applicable directives

Installation Instruction

Publication 1794Ć5.63

1 Use this conductor category information for planning conductor routing . Refer to publication

1770Ć4.1, Industrial Automation Wiring and Grounding Guidelines for Noise Immunity."

Advertising