Chapter summary – Rockwell Automation 1794-ID2 U.MNL INCREMENTAL ENCODER User Manual

Page 51

Advertising
background image

4–7

Writing Configuration to and Reading Status from Your Module with a Remote I/O Adapter

Publication 1794ĆUM015B-EN-P - May 2001

Definition

Bit

Write

Word

Word 1

continued

Bits 06-08

(06 10)

Calibration Control bits - bits 06, 07 and 08

continued

(06-10)

06

Enable bit - When this bit is set (1), the counter can be calibrated.

07

Direction bit - When this bit set (1), calibration is performed in a negative direction; when reset (0), calibration

is performed in a positive direction.

08

Reset bit - Calibration is acknowledged and a new calibration is enabled on a positive edge on this bit.

Bits 09-10

10

09

Gate Control bits

0

0

No gate function on input G

0

1

Counting only if G is high (active)

1

0

Counting only if G is low (inactive)

1

1

Calibration if G is high (active) and ???

Bits 11-12

(13-14)

12

11

Store Control bits - These bits will trigger a Store only if the channel Store status bit (L0 or L1) is

cleared (0).

0

0

Save the counter value on the positive edge of Z (if Store X = 0)

0

1

Save the counter value on the positive edge of G (if Store X = 0)

1

0

Save the counter value on the negative edge of G (if Store X = 0)

1

1

Save the counter value on the positive edge and negative edge of G (if Store X = 0)

Bit 13

Rollover bit - When set (1), the counter counts up to the preset and then restarts at 0. If this bit is reset (0) (not

rollover), the rollover preset value = FFFF (hex = 65535 (decimal).

Bit 14

Store Reset bit - A positive edge on this bit resets Store X in Signals.

Bit 15

Store Reset bit - A positive edge on this bit resets Preset Reached in Signals.

Word 2

Bits 00-15

Preset 0 - Value to load or compare with counter 0

Word 3

Bits 00-15

Preset 1 - Value to load or compare with counter 1

Word 4

Bit 00

Filter A0 enable - When this bit is set (1), anda counter 0 is in mode 000 (pulse counting), signal A0 is filtered by a

digital low pass filter with selectable filter constant.

Bit 01

Filter A1 enable - When this bit is set (1), anda counter 1 is in mode 000 (pulse counting), signal A1 is filtered by a

digital low pass filter with selectable filter constant.

Bit 02Ć07

Unused

Bits 08Ć09

(10Ć11)

09

(11)

08

(10)

Filter Constant bits - This constant is common to both counters.

0

0

73.5kHZ or minimum 0.007ms pulsewidth

0

1

37.8kHz or minimum 0.013ms pulsewidth

1

0

12.8kHz or minimum 0.04ms pulsewidth

1

1

1.2kHz or minimum 0.4ms pulsewidth

Bits 10Ć15

(12Ć17)

Reserved - set to 0

In this chapter, you learned how to configure your module’s features
and enter your data.

Chapter Summary