Publication 1788-UM052B-EN-P - April 2002

Using the NI-FBUS Configurator 4-7

3. Select Set Address from the pop-up menu that opens.

The Set Address window opens.

4. In the New Address field, select the desired address from the

drop-down list.

5. Select the Set to OOS Mode checkbox. Doing so sets the block

to OOS mode, which prevents the device from operating in its
current control system.

6. Click Set.

The NI-FBUS Configurator sets the device resource block to out
of service (OOS) mode before setting the new address. If the
device does not go to OOS mode, the NI-FBUS Configurator
notifies you and you must determine whether to continue setting
the address.

7. After you successfully set the address, you can set the resource

block to the desired mode (typically NORMAL_MODE).