Troubleshooting and Common Questions B-3

Device Problems

If you receive a status of Bad:Device Failure, set the RESTART
parameter in the Block window to Processor or Default. If the
problem persists, replace the device.

If a device does not accept a permanent address, you must set the
device tag. For instructions on setting the tag, refer to the Setting
Device or Block Tags
on page 4-5. If the device already has a tag, the
T3 network parameter might not be the right length. To solve this
problem, remove the device from the active bus and configure its
address separately.

If a device does not accept a new tag, it might be in an invalid state.
To solve this problem, power the device off and on.

Missing Devices

If a device does not appear in the Project window, complete these
steps:

1. Check all connections.

2. Power on the bus.

3. Select Start

Programs

NI-FBUS

Interface Config and

click on the Advanced button.

4. Set the following parameter values.

5. Select Start

Programs

NIFBUS

nifb to restart the nifb

process.

6. Select Start

Programs

NIFBUS

NI-FBUS Configurator

to restart the NI-FBUS Configurator.

Parameter

Value

Number of unavailable nodes

0

InterPduDelay

20

Slot time

10

Max reply delay

8