A-4 Error Messages and Warnings

Warnings

If you receive a warning while using the NI-FBUS Configurator, refer
to this section for a description of the warning and possible solutions.

NIFCONF_ERR_TOO_MANY_LAS_SCHEDULE_ENTRIES The number of LAS schedule entries exceeds the number of available entries in

the LAS device. Choose integer multiple macrocycle values and reduce the
number of data links that go between devices to correct this problem.

NIFCONF_ERR_TYPE_INFO_UNAVAILABLE

The NI-FBUS Configurator cannot read the type information for the object.

NIFCONF_ERR_UNSCHEDULED_TRAFFIC_CONFLICT

The publish time is conflicting with the reserved 128 octet time at the end of a
macrocycle. This time is used for unscheduled traffic.

NIFCONF_ERR_WRONG_TYPE

This object has the wrong type.

Error

Possible Solution

Warning

Possible Solution

NIFCONF_WARN_MEMORY_LOW

The system is low on memory.

NIFCONF_WARN_OBJECT_NOT_WIRED

This object is not connected by wires to any other object.

NIFCONF_WARN_NO_TREND_SELECTED

A trend is wired, but no trend is checked.

NIFCONF_WARN_TREND_NOT_WIRED

A trend is selected, but not wired to a device.

NIFCONF_WARN_PROJECT_ERRORS

There are errors that might cause problems in the download of the configuration. Look at
the Errors tab in the Status window.