Publication 1747-UM002A-US-P - June 2000

6-48 Library of Routines

Description:

To guarantee that a series of calls to OC_ReadInputImage read data
from a single input scan, OC_ReadInputImage can first be called to
read the entire input image into a local buffer pointed to by

imagebuf

, with the

inpimgcpy

pointer set to NULL and

slotnum

set

to -1. The

imagebuf

buffer can then be passed as

inpimgcpy

in

subsequent OC_ReadInputImage calls to retrieve the slot data from
the copy of the input image. This preserves input image file integrity
across multiple calls to OC_ReadInputImage.

If file integrity is not necessary, the host application can set

inpimgcpy

to NULL and access data directly from shared memory.

Return Value:

Considerations:

Supported in the DOS API library and the Windows NT API library

Example:

HANDLE

Handle;

WORD

inputdata[2];

int

retcode;

retcode =

OC_ReadInputImage( Handle, NULL, 6, 0, 2,

inputdata );

/* Read slot 6 data, first 2 words, directly from the input

image */

/* table to inputdata buffer */

Name:

Value:

Description:

SUCCESS

0

input image was read successfully

ERR_OCACCESS

2

handle

does not have access to scanner

ERR_OCPARAM

8

parameter contains invalid value

ERR_OCSCANCFG

14

scanner has not been configured

ERR_OCSLOT

12

slot number is invalid

Advertising