Oc_gettemperature, Oc_gettemperature -35 – Rockwell Automation 1747-PCIS API Software - Open Controller User Manual

Page 95

Advertising
background image

Publication 1747-UM002A-US-P - June 2000

Library of Routines 6-35

Return Value:

Considerations:

Supported in the DOS API library and the Windows NT API library

Example:

HANDLE

Handle;

BYTE

sw_pos;

int

retcode;

retcode = OC_GetSwitchPosition( Handle, &sw_pos );

if ( sw_pos == SWITCH_BOTTOM )

OC_SetScanMode ( Handle, SCAN_IDLE );

OC_GetTemperature

OC_GetTemperature reads the current temperature of the 1746 I/O
PCI Interface’s built-in thermometer.

Syntax:

int

OC_GetTemperature(HANDLE handle, BYTE*temp);

Parameters:

Description:

The temperature is updated every 10 seconds by the scanner.

The optimal operating temperature range for the 1746 I/O PCI
Interface is 0° to 60°C. When OC_GetTemperature returns a value of
75_ C or higher, the 1746 I/O PCI Interface is operating beyond its
optimal operating temperature range and you need to correct the
situation.

The scanner must be initialized before you can monitor the
temperature.

Name:

Value:

Description:

SUCCESS

0

switch position was read successfully

ERR_OCACCESS

2

handle

does not have access to scanner

ERR_OCINIT

5

scanner has not been initialized, see OC_InitScanner

Parameter:

Description:

handle

Must be a valid handle returned from OC_OpenScanner

temp

Returns the temperature in degrees Celsius