Parameters:

Description

Once the Host Watchdog is enabled, the host application must call
OC_PetHostWatchdog more often than the time specified as the
watchdog timeout. If the host application does not call
OC_PetHostWatchdog for a time longer than the watchdog timeout,
then the action specified by

mode

is performed.Return Value

Return Value:

Considerations:

Supported in the DOS API library and the Windows NT API library

Parameter:

Description:

handle

Must be a valid handle returned from OC_OpenScanner

mode

If

mode

is:

WATCHDOG_IGNORE

The host-to-scanner watchdog is
disabled (default).

WATCHDOG_IDLE

A watchdog timeout causes the scanner
to fault. The status LED is set to flashing
red, the I/O is reset, I/O scanning stops,
and internal scanner error of 0x0B is set,
and the major error code is set to 0x40.
Use OC_ClearFault before the scanner can
be set to Scan mode.

WATCHDOG_RESET

A watchdog timeout forces a hard reset of
the controller and scanner..
If the mode is WATCHDOG_RESET, the
control application must disable this
watchdog before exiting. If this watchdog
is not disabled, the controller and scanner
experience hard resets once the timeout
delay has expired.
The WATCHDOG_RESET mode is not
available on the 1747-PCIS and will return
ERR_OCNOTSUPP.

delay

Specifies the watchdog timeout in multiples of 100ms and can have
any value from 1 (100ms) to 65535 (6553.5s).

Name:

Value:

Description:

SUCCESS

0

host watchdog was set successfully

ERR_OCACCESS

2

handle

does not have access to scanner

ERR_OCINIT

5

scanner has not been initialized, see OC_InitScanner

ERR_OCPARAM

8

parameter contains invalid value