Library of Routines 6-3

OC_CloseScanner

This function must always be called before exiting the application.

Syntax:

int

OC_CloseScanner(HANDLE handle);

Parameters:

Description:

This function releases control of the scanner device, releases the
interrupt assigned by OC_OpenScanner, and disables the segment
address assignment.

Return Value:

Considerations:

Supported in the DOS API library and the Windows NT API library

Example:

HANDLE

Handle;

int

retcode;

retcode = OC_CloseScanner( Handle );

Parameter:

Description:

handle

Must be a valid handle returned from OC_OpenScanner

ATTENTION

!

The system might become unstable if you don’t call
OC_CloseScanner before exiting the application.

Name:

Value:

Description:

SUCCESS

0

scanner was closed successfully

ERR_OCACCESS

2

handle

does not have access to the scanner