Error Codes A-3

The error code data provides information specific to the cause of all
extended errors, except 0xF0. The first byte of the error code data
contains a subsystem identifier with the following information:

The second byte of the error code data provides details about the
subsystem identifier with the following information:

0x60 - 0x8F

Module specific errors (see I/O module documentation)

0x90

MINT occurred on disabled slot

0x91

PINT occurred on disabled slot

0x93

Unsupported module error

0x94

Module has been inserted or reset

0xF0

Internal scanner error

Subsystem ID:

Description:

0x06

Scanner Communications

0x08

Backplane Interface (module I/O)

Error Code:

Description:

0x00

Download error - invalid directory file pointer block

0x01

Download error - change to Idle mode failed

0x02

Download error - configuration file CRC failed (byte 1
contains the file number)

0x03

Download error - directory CRC failed

0x04

Download error - input or output image exceeds partition
allocation (byte 1 contains 0 for output image, 1 for input)

Extended Error