1-6 Overview

In addition to providing access to the control scanner, the dual port
memory also provides non-volatile (optional battery-backed) storage
for:

I/O values

application parameters (timers, counters, presets)

Scanner Modes

In both application types, the scanner CPU operates in six
basic modes:

performing POST (power-on self test)

waiting for host initialization

Idle

Scan

Faulted

non-recoverable fault

After the scanner successfully completes the POST, the scanner waits
for an initialization complete command from the application. Once the
scanner receives this command, the scanner enters Idle mode.

Before the scanner can enter Scan mode, the application must
download a valid I/O configuration to the scanner.

If a recoverable fault occurs, the scanner enters Faulted mode. Use the
OC_ClearFault API function to clear the fault before the scanner can
resume operating in Scan mode.

If a non-recoverable fault occurs, reset the scanner (cycle power).
Some possible non-recoverable faults include:

POST failure

background diagnostic failure

internal watchdog timeout