Example queue 5 -60, Example queue 5, Number of records – Rockwell Automation DAG6.5.8 APPLICATION GUIDE SCADA SYSTEM User Manual
Page 128

Publication AG-UM008C-EN-P - February 2005
3-60 Configuring MicroLogix 1100/1200/1500 Controllers
Number of Records
Using Queue 0 as an example, each record consumes:
In this example, each record consumes 18 bytes. So if one queue was
configured, the maximum number of records that could be stored
would be 2730. The maximum number of records is calculated by:
Maximum Number of Records = Data Log File Size/Record Size
= 48K bytes/18 bytes
= (48)(1024)/18
= 2730 records
Example Queue 5
Record Field
Memory Consumption
Date
2 bytes
Time
2 bytes
N7:11
2 bytes
L14:0
4 bytes
T4:5.ACC
2 bytes
I1:3.0
2 bytes
B3:2
2 bytes
Integrity Check
2 bytes
Total
18 bytes
Table 3.12 Queue 5 (Time = ✔, Delimiter = TAB)
Time
N7:11
I1:3.0
I1:2.1
Record 0
20:00:00
TAB
2315
TAB
8190
TAB
4465
Record 1
20:30:00
TAB
2400
TAB
8210
TAB
4375
Record 2
21:00:00
TAB
2275
TAB
8150
TAB
4335
Record 3
21:30:00
TAB
2380
TAB
8195
TAB
4360
Record 4
22:00:00
TAB
2293
TAB
8390
TAB
4375
Record 5
22:30:00
TAB
2301
TAB
8400
TAB
4405
Record 6
23:00:00
TAB
2308
TAB
8100
TAB
4395