5-2 Configuring SLC 500 Processors with 1747-KE Interface Modules
Figure 5.1 Configuring SLC 500 Processor with 1747-KE Module
Installing the Processor
For details about installing the modular processor, see SLC 500
Modular Hardware Style User Manual, publication 1747-UM011.
Installing the 1747-KE
Interface Module
To install the interface module, do the following:
1. To allow an ASCII terminal to communicate with the module,
place the module in series B functionality Configuration Mode
by setting JW4 as follows:
2. Since the ASCII terminal communicates with the module via an
RS-232 connection, verify that the CONFIG port is configured for
RS-232 by verifying this setting for JW1:
3. Since the DF1 port connects to a modem, verify that the port is
configured for RS-232 by verifying this setting for JW2:
4. Install the module into a powered-down chassis.
modem
1
2
3
4
Configuration Mode Setting
CONFIG port is configured for RS-232
DF1 port is configured for RS-232