Configuring SLC 5/03, 5/04, and 5/05 Processors 4-11
Use Worksheet 4.1 (page D-14) for an example configuration and to
record your station’s configuration.
Table 4.1 shows the parameters for configuring an SLC 5/03, 5/04, or
5/05 processor as a master station using standard-communication
mode to talk to slave stations.
3. On the Channel 0 tab, choose
DF1 Half-Duplex Master for
your Driver.
4. Choose a Standard Polling
Mode.
5. Configure the rest of the
communication driver
characteristics according to
See Table 4.1 on page 4-11.
Table 4.1 SLC 5/03, 5/04, or 5/05 Master Using Standard-Communication Mode
Tab
Parameter
Selections
General
Diagnostic File
SLC 5/03 (OS 302 C or higher), 5/04 (OS 401 C or higher) and 5/05 only. Select an
unused file (9 to 255) to store channel status information. You must define a
diagnostic file in order to be able to view channel 0 status. See Table 4.3 on
page 4-16 for a file description.