Configuring the 1747-ke interface module, Configuring the 1747-ke, Interface module -4 – Rockwell Automation DAG6.5.8 APPLICATION GUIDE SCADA SYSTEM User Manual
Page 190: Prepare to configure the driver -4, Prepare to configure the driver

Publication AG-UM008C-EN-P - February 2005
5-4 Configuring SLC 500 Processors with 1747-KE Interface Modules
Configuring the 1747-KE
Interface Module
To configure the interface module with an ASCII terminal:
•
prepare to configure the driver
•
configure the DF1 protocol driver, and
•
save the configuration
Prepare to Configure the Driver
1. Connect an ASCII terminal or personal computer running
terminal emulation software to the interface module’s CONFIG
port.
2. Turn on power to the chassis containing the interface module.
3. Run the ASCII terminal emulation software, and configure the
software to match the default CONFIG port parameters, which
are the following:
4. Configure the DF1 port as shown in Figure 5.3.
DH-485/RS-232C
ACT
485
CFG
DF1
Fault
BA LOW
H/D
F/D
41200
ASCII
9-pin female 9-pin female
2
2
3
3
5
5
Parameter
Selections
Baud rate
1200
Bits per character
8
Parity
none
Stop bits
one